Fire door assemblies must be inspected and tested annually by a qualified person, and the results documented. Most commercial buildings in Ontario have fire doors that would fail that inspection today — usually for reasons the building owner has no idea are problems.

Gamble Lock inspects, documents and repairs fire-rated door assemblies for commercial, retail, institutional and multi-site property portfolios across Ontario and nationally. We have been servicing commercial door openings since 1971.

What the requirement actually is

The Ontario Fire Code requires that closures in fire separations be maintained in operating condition. For fire-rated door assemblies, the referenced standard is NFPA 80, Standard for Fire Doors and Other Opening Protectives, which sets out an annual inspection and testing regime and requires that records be retained and made available to the authority having jurisdiction.

In practice this means three things for a building owner or property manager:

A fire door that has been painted over, wedged open, drilled for a sign, or fitted with a closer that no longer shuts it is not a compliant assembly — regardless of whether it was compliant the day it was installed.

The 13-point inspection

NFPA 80 sets out the criteria a swinging fire door assembly is inspected against. Every opening we inspect is assessed on all thirteen:

  1. Labels are present and legible
  2. No holes or breaks in the door or frame
  3. Glazing, glass kits and glazing beads are intact and securely fastened
  4. Door, frame and hardware are in proper working order
  5. No missing or broken parts
  6. Door clearances are within allowable limits
  7. The closer or spring hinges are operational and the door is self-closing
  8. On pairs, the coordinator closes the leaves in the correct sequence
  9. The door self-latches in the closed position
  10. No auxiliary items interfere with operation
  11. No field modifications have been made that would void the label
  12. Gasketing and edge seals, where required, are present, continuous and of the correct type
  13. Signage does not exceed the permitted coverage and is not attached with metal fasteners

What we find most often

After decades of inspecting commercial openings, the same failures come up again and again. None of them are exotic, and most were created by well-meaning people solving a different problem:

How fire door inspection is priced

Inspection is quoted per opening. We do not publish a rate card, because the per-door number moves considerably depending on the job — a quoted price that ignored these factors would be wrong often enough to be useless to you.

What actually drives it:

We will quote within two business days of knowing your site count and approximate door count. If you do not know your door count, we can establish it on the first visit.

Repairs are quoted separately once the inspection identifies what needs correcting. Many deficiencies — closer adjustment, strike alignment, gasketing replacement, hardware swaps — are corrected on the spot during the inspection visit where the parts are on the truck, which avoids a second mobilisation charge. We will tell you before we start which items we can close out same-visit.

What you get

Every inspection produces a written record you can hand to a fire inspector:

For portfolio clients we maintain the schedule between visits, so year two is faster and cheaper than year one.

We repair what we find

An inspection report on its own does not make a building compliant. The advantage of using a door company rather than an inspection-only firm is that the same organisation closes out the deficiencies.

Gamble Lock carries hollow metal doors and frames, fire-rated hardware, closers, exit devices, gasketing and glazing, and we fabricate and install replacement openings where a door is beyond repair. That includes label-compliant repairs that preserve the rating rather than voiding it.

Multi-site and national portfolios

We run scheduled inspection programs across national retail, banking and property management portfolios, coordinated centrally and reported in a consistent format across every site. If you manage buildings in more than one province, we can run the whole program through a single point of contact rather than a separate vendor in each market.

Common questions

How often do fire doors need to be inspected?

Annually, by a qualified person, with records retained. Newly installed assemblies are also subject to an acceptance inspection before being put into service.

Who is allowed to inspect a fire door?

NFPA 80 requires inspection by a person with knowledge and understanding of the operating components of the type of door being subject to testing. In practice, authorities having jurisdiction expect a qualified door and hardware technician, not general building staff.

What happens if a door fails?

Deficiencies must be corrected without delay. A failed opening is not automatically a code violation if it is being actively remediated — what creates exposure is an uninspected, undocumented building.

Can a fire door be repaired, or does it have to be replaced?

Most deficiencies are repairable. Closers, latching hardware, gasketing, glazing and strikes can all be corrected without affecting the rating, provided the replacement components carry the correct listing and the work is done to the standard. Doors with extensive field modification or structural damage generally need replacement.

Book a fire door inspection

Tell us how many buildings and roughly how many fire-rated openings you have, and we will come back with a per-opening rate and a proposed schedule.