What a Door Inspection Report Should Include

Key points

  • A useful report identifies every opening individually, with its location.
  • Each deficiency should say what is wrong, why it matters and what will fix it.
  • Fire door inspection records have to be signed and kept. NFPA 80 sets three years unless your jurisdiction says otherwise.

A door inspection is only as good as the report that comes out of it. The report is what you budget from, what you hand to a fire inspector, and what you rely on if something goes wrong later. This guide sets out what a report should contain and how to tell a good one from a poor one.

Commercial steel door with exit hardware

What every report should contain

The building and the inspector

The site name and address, the date of the inspection, the name of the person who carried it out and the company they work for. For fire door inspections, NFPA 80 requires these details and requires the inspector to sign the record.

Each opening, identified

Every door should appear on its own line with a location clear enough that someone else could walk to it: floor, room or corridor, and a door number where the building has them. A report that says 14 doors failed without saying which 14 cannot be acted on.

What the opening is

The type of door and frame, whether it is a single door or a pair, and its fire rating where it has one. The rating matters because it decides which repairs are allowed and which hardware may be fitted.

What was checked and what was found

For a fire door, the inspection covers a defined list of points, including labels, clearances, the closer, latching, hinges, glazing, seals and any field modifications. The report should show the result for each opening and describe every deficiency in plain words. A good description reads like this: latch does not engage when the door closes from 30 degrees, strike needs adjusting.

Priority

Deficiencies are not equal. A fire door that will not latch is a life safety problem. A worn sweep is not. The report should rank findings so the urgent ones are dealt with first.

Recommended action

For each deficiency, the repair that will correct it: adjust, repair or replace. This is the part you budget from, so it should be specific.

Photographs

A photograph of each deficiency is good practice. It removes arguments about what was found and helps the person doing the repair arrive with the right parts.

How to use the report

  • Deal with life safety first. NFPA 80 says fire door deficiencies are to be repaired without delay.
  • Group the rest by trade and by site, so repairs can be done in one visit where possible.
  • Record the corrections. A deficiency list with no record of the repair is only half of the file a fire inspector will ask to see.
  • Keep the records. NFPA 80 sets a retention period of three years for inspection records unless the jurisdiction specifies another, and electronic records are acceptable.
  • Compare year over year. The same door failing every year points to a cause that a repair is not reaching, such as traffic, abuse or the wrong hardware for the opening.

Signs of a poor report

  • Door counts with no locations.
  • Pass or fail with no explanation of what failed.
  • The same wording copied against every door.
  • No name, date or signature.
  • A quote for replacement with no description of the deficiency behind it.

Reports across a portfolio

For multiple sites, the format matters as much as the content. If every site is reported the same way, with the same categories and priorities, you can compare buildings and plan a budget across all of them. Ask for the format to be agreed before the first inspection.

Our fire door inspection and preventive maintenance pages describe how we report.

This guide is general information. Record-keeping requirements vary by province, and the authority having jurisdiction has the final say.